- FIRE HYDRANT FLOW TEST - PER NFPA 291 TEST6
- DEVELOPMENT5
- FIRE HYDRANT FLOW TEST - WITNESS ONLY1
Recent permits
The 8 newest on file.
| Date | Type | Work | Jurisdiction | Job value |
|---|---|---|---|---|
| Oct 15, 2026 | DEVELOPMENT | Development - Roads hydrants. | Brunswick County | — |
| Aug 4, 2026 | DEVELOPMENT | Fire Plan Review - Fire Development | Brunswick County | — |
| Aug 4, 2026 | FIRE HYDRANT FLOW TEST - PER NFPA 291 TEST | NFPA 291 - Fire Hydrant Flow Test Hydrant flow test passed Hydrant 3467 flowed 1060 gpm @ 40 psi 24 elev 12' main Static 64 Res 62 5626 gpm @ 20 psi | Brunswick County | — |
| Jul 28, 2026 | FIRE HYDRANT FLOW TEST - WITNESS ONLY | Witness Fire Hydrant Flow Test | Brunswick County | — |
| May 28, 2026 | FIRE HYDRANT FLOW TEST - PER NFPA 291 TEST | Hydrant flow test Passed. Main-30' Static-90 psi Residual-75 psi Elevation 31' Flow-1350 gpm at 65 psi Calculated flow- 3102 gpm at 20 psi. | Brunswick County | — |
| Apr 28, 2026 | DEVELOPMENT | Development Roads | Brunswick County | $1,045,100 |
| Mar 5, 2026 | FIRE HYDRANT FLOW TEST - PER NFPA 291 TEST | Perform Fire Hydrant Flow Test Hydrant flow test Passed Hydrant 342 static 65 / Residual 60 Flow hydrant 343 1130 gpm @ 45 psi Elevation 49 / 30' main / 3734 gp | Brunswick County | — |
| Feb 18, 2026 | FIRE HYDRANT FLOW TEST - PER NFPA 291 TEST | Fire Hydrant Flow Test NFPA 291 Flow test. Passed. 12' Main Static - 58 psi Residual-48 psi Flow-35 psi at 1000 gpm Calculated flow- 2056 gpm at 20 psi Elevatio | Brunswick County | — |